Extinguishing And Fire Alarm Control Panel KFP-CX3
KFP-CX3 is a conventional extinguishing and fire alarm control panel for small to mid-sized systems. It has three fire detection groups and several fire push-button and control inputs that control extinguishing activities at a separate extinguishing area. 20 detectors can be integrated into single fire detection group.
- Modern, stylish design
- 3 detection zones (max 20 detectors/ zone)
Control Panel | KFP-CX3 |
Power supply | 110 VAC/60 Hz or 240 VAC/50 Hz |
Tolerance | +10 % / -15 % |
Maximum current consumption | 3.15 A @ 110 / 1.5 A @ 240 VAC |
Cable | 3 x 1.5 mm² (phase, neutral, ground) |
Batteries | 2 x 12V 12 Ah (SLA) |
Panel supply | 4A @ 24 VDC |
Quiescent current (no devices) | 0.39 A |
Alarm current (no devices) | 2.78 A |
Zones | 3 |
Output voltage | 22 VDC (18-24 VDC) |
Load (max) | 65 mA |
Cable resistance (max) | 40 ohm |
Cable capacitance (max) | 500 nF |
(Max) devices per zone | 20 |
Supervised inputs | 6 |
Use | MCP Start, MCP Hold, MCP Abort, Pressure Switch, Gas Flow, Door Monitor |
Non-supervised inputs | 2 |
Use | Auto/Manual mode, Remote Reset |
Supervised outputs | 4 |
Use | Fire Sounders, Extinguishing Sounders, Optical Indications, Actuator |
Fire Sounders | 2 x 500 mA @ 24 VDC |
Optical Indications | 1 x 500 mA @ 24 VDC |
Actuator | 1 x 1 A @ 24 VDC |
Non-supervised outputs | 4 |
Use | Hold Mode, Abort Mode, Manual Mode, Release Indication |
Specification | 4 x 2 A @ 30 V |
Output voltage | 24 V (21-28 V) |
Load (max) | 250 mA |
Storage temperature | -20 ºC – +70 ºC |
Working temperature | – 5ºC – +50 ºC |
Relative humidity | 10-95 % |
IP classification | 30 |
Size (h x w x d) | 480 x 440 x 140 mm |
Weight (without batteries) | 3.9 kg |
Colour | White |
Cable entry | Ø20 mm |
Top | 20 |
Rear | 26 |
Bottom | 2 |