HL-22 ESFR

Reliable Logo
Approvals
SIN-numbers
RA1011

Description

The HL22 Early Suppression Fast Response (ESFR) Sprinkler is intended for use against severe fire challenges. This sprinkler is designed to respond quickly to growing fires with a high volume of water discharge to “suppress” rather than “control” fires at lower pressures

The HL22 Sprinkler utilizes a levered fusible alloy solder link in either 74°C or 100°C temperature ratings. FM Global considers this a “Quick Response” storage sprinkler for use in data sheet 8- 9. The sprinkler has a Nominal K Factor of 22.4 (320 metric) and will deliver approximately 112 gpm (424 L/min) of water at 25 psi (1,7 bar).

Design Criteria

Sprinkler Position: Pendent, align frame arms with the pipe. Deflectors should be parallel with the ceiling or roof.
System Type: Wet Pipe Systems Only
Max. area of coverage: 9,3m2, greater coverage area are allowable in some cases
Min. area of coverage: 5,8m2
Max. slope celling: 9,5°
Max. spacing: 3,7m ( for building heights up to 9,1m), 3,1m ( for building heights greater than 9.1m)
Min. spacing: 2,4m
Deflector distance from wall: At least 102mm from walls, and no more than one-half the allowable distance permitted between sprinklers
Deflector to Top of Storage: Min. 914mm
Deflector to ceiling Distance: 152-457mm per NFPA 13, 152-356mm per FM 2-2.
Center Line of Thermal Sensing Element To Ceiling Distance: 50-425mm smooth celling, 100-425 uneven celling

Listings and Approvals

1. Listed by Underwriters Laboratories, Inc. and UL certified for Canada (cULus).
2. FM Approved as a quick-response, storage and nonstorage sprinkler (FM).
3. VdS Schadenverhütung (VdS).
4. Loss Prevention Certification Board (LPCB).

Technical Specifications

Sprinkler Temp. Link Color Max.Ambient Temp. Type K-value Thread size Max.
Working pressure
74ºC Black 38ºC Pendent 320 1”NPT or 1″BSPT 12,1 bar
100ºC White 66ºC Pendent 320 1”NPT or 1″BSPT 12,1 bar