Description
The HL22 Early Suppression Fast Response (ESFR) Sprinkler is intended for use against severe fire challenges. This sprinkler is designed to respond quickly to growing fires with a high volume of water discharge to “suppress” rather than “control” fires at lower pressures
The HL22 Sprinkler utilizes a levered fusible alloy solder link in either 74°C or 100°C temperature ratings. FM Global considers this a “Quick Response” storage sprinkler for use in data sheet 8- 9. The sprinkler has a Nominal K Factor of 22.4 (320 metric) and will deliver approximately 112 gpm (424 L/min) of water at 25 psi (1,7 bar).
Design Criteria
Sprinkler Position: Pendent, align frame arms with the pipe. Deflectors should be parallel with the ceiling or roof.
System Type: Wet Pipe Systems Only
Max. area of coverage: 9,3m2, greater coverage area are allowable in some cases
Min. area of coverage: 5,8m2
Max. slope celling: 9,5°
Max. spacing: 3,7m ( for building heights up to 9,1m), 3,1m ( for building heights greater than 9.1m)
Min. spacing: 2,4m
Deflector distance from wall: At least 102mm from walls, and no more than one-half the allowable distance permitted between sprinklers
Deflector to Top of Storage: Min. 914mm
Deflector to ceiling Distance: 152-457mm per NFPA 13, 152-356mm per FM 2-2.
Center Line of Thermal Sensing Element To Ceiling Distance: 50-425mm smooth celling, 100-425 uneven celling
Listings and Approvals
1. Listed by Underwriters Laboratories, Inc. and UL certified for Canada (cULus).
2. FM Approved as a quick-response, storage and nonstorage sprinkler (FM).
3. VdS Schadenverhütung (VdS).
4. Loss Prevention Certification Board (LPCB).
Sprinkler Temp. | Link Color | Max.Ambient Temp. | Type | K-value | Thread size | Max. Working pressure |
74ºC | Black | 38ºC | Pendent | 320 | 1”NPT or 1″BSPT | 12,1 bar |
100ºC | White | 66ºC | Pendent | 320 | 1”NPT or 1″BSPT | 12,1 bar |