G5-80, G5-56, G5-42 & G5-28

Reliable Logo
Approvals
SIN-numbers
RA3411, RA3412, RA3413, RA3415, RA3417, RA4014

Description

The Reliable Model G5-80, G5-56, G5-42 and G5-28 uses a proven quick response fusible element in a standard style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate assembly. The threaded engagement provides ¾” (19mm) of cover adjustment. The flat cover plate is attached to the skirt using either 57°C or 74°C ordinary temperature classification solder. When the ceiling temperature rises, the solder holding the flat cover plate melts, the flat cover plate released thus exposing the sprinkler inside to the rising ambient temperature. The subsequent fusing of the element opens the waterway and causes the deflector to distribute the water. Any secure engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling.

Installation

Do not install the G5-80, G5-56, G5-42 and G5-28 in ceilings which have positive pressure in the space above. • Cut a 25 /8” inch (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model FC Wrench. The wrench has a socket drive which is inserted into the body of the sprinkler. When installing a sprinkler the wrench is first positioned into the sprinkler/cup assembly until the wrench socket engages the body of the sprinkler. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/ CUP ASSEMBLY. Install the cover plate by hand turning the cover in the clockwise direction until it is tight against the ceiling. A protective cap is provided to protect the drop-down sprinkler deflector from damage which could occur during construction before the cover plate is installed. The cap is factory installed inside the sprinkler cup. Remove cap to install sprinkler, then reinstall cap until the cover plate is installed.

Approvals & Listings

1. Underwriters Laboratories Inc. and cULus –
Quick Response
• G5-80, G5-56 – Light Hazard & Ordinary Hazard
• G5-42 – Light Hazard
• G5-28 – Light Hazard
2. Factory Mutual Research Corp. (FM) –
Standard Response
• G5-56, G5-28 & G5-80F
3. Loss Prevention Council (LPCB, UK) –
Standard Response
• G5-56 – Light Hazard & Ordinary Hazard
4. VdS Schadenverhütung GmbH – Standard Response
5. EC-Certificate of Conformity 0832-CPD-2062

Technical Specifications

Model Response K-value Thread size Approvals SIN
G5-80 Quick Response 115 ¾” NPT 1 RA3412
G5-56 Quick Response 80 ½” NPT 1,2,3,4,5 RA3415
G5-42 Quick Response 60 ½” NPT 1 RA3413
G5-28 Quick Response 40 ½” NPT 1,2 RA3411

Temperature Rating

Sprinkler Temp. Cover Plate Temp. Max.Ambient Temp.
74ºC 57ºC 38ºC
100ºC 74ºC 66ºC