Description
Reliable DH80 Series sprinklers are fast (Quick Response) automatic extended protection industry sivusprinklereitä (HSW) light sprinkler class applications. Typical applications include walkways or other long narrow spaces always the size of 8,5m x 4,3m up. the temperature sensitive part of the sprinklers is 3 mm glass capsule. Concealed nozzle models use SWC model of the protective cover.
Features
1. Nominal K-value= 115
2. Horizontal Sidewall, HSW
3. Protection narrow spaces the size of up to 8,5m x 4,3m
4. Sprinkler distance from the ceiling 102-305mm
5. Min.gap 3,6 m
6. Thread size3/4″NPT
7. Max.Working pressure 17,2 bar
Listings and Approvals
1. Listed by Underwriters Laboratories Inc. and
UL certified for Canada (cULus)
2. NYC MEA 258-93-E
Sprinkler Temp. | Glass Bulb color | SWC Cover Temp. | Max.Ambient Temp. |
57ºC | Orange | 57ºC | 38ºC |
68ºC | Red | 57ºC | 38ºC |