Reliable Logo
Approvals
SIN-numbers
RA1325, RA1323, RA1321, RA1314, RA1313, RA1311, RA1375, RA1385, RA1335

Description

The F156, F142, F1XLH & F128 Series Glass Bulb Sprinkler combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler. Whether installed on exposed piping or in an office ceiling, it is functional and attractive. Beautifully versatile is the description for the Reliable Models F156, F142, F1XLH & F128 Series Recessed glass bulb sprinkler. Recessing the F156, F142, F1XLH & F128 Series enhances its already low profile decorative appearance, and facilitates a rapid and perfect installation. The nozzles are functional and good-looking as well as directly to the bare piping the suspended ceiling or wall mounted.

F1-series of sprinklers has a 5 mm glass capsule. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. At normal temperatures, the glass bulb contains the fluid in both the liquid phase and in the vapor phase. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distribute the discharging water. The glass capsule color indicates the sprinkler trigger temperature (see the Table on the bottom of the page).

Application areas

F1 Series sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction.

Installation

When installing Model F156, F142, F1XLH & F128 Recessed Sprinklers use the Model GFR2 Sprinkler Wrench. Any other type of wrench may damage these sprinklers. A leak tight ½” NPT (R1/2) sprinkler joint can be obtained with a torque of 10,8 – 24,4 N-m. Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers

Models

F156 (K=80)
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall

F142 (K=60) and F128 (K=40)
Standard Upright
Standard Pendent

Color

Standard finishes and colors: Chrome and Brass, other colors and finishes are available on special order.

Listings and Approvals

1. Underwriters Laboratories Inc. and certified for Canada (cULus)
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhütung GmbH
5. EC Certificate: 0786-CPD-40237 (RA1314), 0786-CPD-40253 (RA1325), 0786-CPD-40254 (RA1375)

UL listing categories
Sprinklers, Automatic & Open (VNIV)

Technical Specifications

Model K-value Response Thread size Max.working pressure Min.working pressure
F156 80 Standard Response ½” NPT 12 bar 0,5 bar
F142 60 Standard Response ½” NPT 12 bar 0,5 bar
F128 40 Standard Response ½” NPT 12 bar 0,5 bar

Material Data

Frame Deflector Load Screw Cup Washer Bulb
DZR Brass
QM Brass
**Low-lead Brass
CDA 260,
CDA 220
or
CDA 510
CDA 360
or
CDA 544
CDA 651
or
CDA 693
Nickel Alloy 440 or 360
PTFE Adhesive Tape
Glass

Temperature Ratings

Sprinkler Temp. Max.Ambient Temp. Bulb Color
57ºC 38ºC Orange
68ºC 38ºC Red
79ºC 66ºC Yellow
93ºC 66ºC Green
141ºC 107ºC Blue
182ºC 149ºC Violet