[right_side] [feat_img]
[left_side]
Extinguishing And Fire Alarm Control Panel KFP-CX3
KFP-CX3 is a conventional extinguishing and fire alarm control panel for small to mid-sized systems. It has three fire detection groups and several fire push-button and control inputs that control extinguishing activities at a separate extinguishing area. 20 detectors can be integrated into single fire detection group.
- Modern, stylish design
- 3 detection zones (max 20 detectors/ zone)
[full_width]
| Control Panel | KFP-CX3 |
| Power supply | 110 VAC/60 Hz or 240 VAC/50 Hz |
| Tolerance | +10 % / -15 % |
| Maximum current consumption | 3.15 A @ 110 / 1.5 A @ 240 VAC |
| Cable | 3 x 1.5 mm² (phase, neutral, ground) |
| Batteries | 2 x 12V 12 Ah (SLA) |
| Panel supply | 4A @ 24 VDC |
| Quiescent current (no devices) | 0.39 A |
| Alarm current (no devices) | 2.78 A |
| Zones | 3 |
| Output voltage | 22 VDC (18-24 VDC) |
| Load (max) | 65 mA |
| Cable resistance (max) | 40 ohm |
| Cable capacitance (max) | 500 nF |
| (Max) devices per zone | 20 |
| Supervised inputs | 6 |
| Use | MCP Start, MCP Hold, MCP Abort, Pressure Switch, Gas Flow, Door Monitor |
| Non-supervised inputs | 2 |
| Use | Auto/Manual mode, Remote Reset |
| Supervised outputs | 4 |
| Use | Fire Sounders, Extinguishing Sounders, Optical Indications, Actuator |
| Fire Sounders | 2 x 500 mA @ 24 VDC |
| Optical Indications | 1 x 500 mA @ 24 VDC |
| Actuator | 1 x 1 A @ 24 VDC |
| Non-supervised outputs | 4 |
| Use | Hold Mode, Abort Mode, Manual Mode, Release Indication |
| Specification | 4 x 2 A @ 30 V |
| Output voltage | 24 V (21-28 V) |
| Load (max) | 250 mA |
| Storage temperature | -20 ºC – +70 ºC |
| Working temperature | – 5ºC – +50 ºC |
| Relative humidity | 10-95 % |
| IP classification | 30 |
| Size (h x w x d) | 480 x 440 x 140 mm |
| Weight (without batteries) | 3.9 kg |
| Colour | White |
| Cable entry | Ø20 mm |
| Top | 20 |
| Rear | 26 |
| Bottom | 2 |