[right_side]
[feat_img]
Approvals
[sin numbers=”RA5114″]
[left_side]
Description
The Reliable Model G5-56 Dry sprinkler is a Dry Pendent sprinkler, where the sealing washer is located at the inlet end of the sprinkler assembly. The position of the sealing washer is controlled by a fusible element at the opposite end of the sprinkler assembly. The sprinkler is installed with the fusible element at the ceiling of a protected space that may be subject to freezing temperatures and the inlet orifice located in a heated area above the ceiling. Operation of the fusible element allows the sealing washer to move out of the inlet orifice admitting water from the supply piping. The sprinkler uses a fast-response fusible element with an Ordinary, 165°F (74°C), or Intermediate, 212°F (100°C), temperature classification.
Technical Specifications
K-value: 80
Thread size: 1″
Max.working pressure: 12 bar (tested 34,5 bar)
Sprinkler available in lengths from : 4½”-48” (114mm-1219mm) ¼”:n (6,35 mm) increments.
Installation key: Model FC
*Check the Datasheet to determine the right lengths (A-dimension) for a model
Listings and Approvals
1. Listed by Underwriters Laboratories and Certified for Canada (cULus) as a Quick-response sprinkler for Light and Ordinary Hazard occupancies.
2. FM Approved as a Standard-response sprinkler.
UL Guide Number VNIV, Sprinklers, Automatic and Open.
Sprinkler Temp. | Cover plate Temp. | Max.Ambient Temp. |
74ºC | 57ºC | 38ºC |
100ºC | 74ºC | 66ºC |