F1FR56 QREC (DN15)

Reliable Logo
Approvals
SIN-numbers
RA2845, RA2865

Description

Reliable Models F1FR56 QREC and F1FR56 QREC Recessed Sprinklers are quick response sprinklers which combine the durability for a standard sprinkler with the attractive low profile of a decorative sprinkler. The Models F1FR56 QREC and F1FR56 QREC Recessed Automatic Sprinklers utilize a 3.0mm frangible glass bulb. These sprinklers have demonstrated response times in laboratory tests which are five times faster than standard response sprinklers. This quick response enables these sprinklers to apply water to a fire much faster than standard sprinklers of the same temperature rating. Model F1FR56 QREC Quick Response Extended Coverage Concealed Sprinkler is an attractive, low profile concealed sprinkler assembly. This sprinkler assembly utilizes a Model F1FR56 QREC pendent sprinkler in a Model CCP cup and push-on thread-off cover plate assembly. The cup is securely factory threaded on the sprinkler’s inlet end. The assembly is shipped with a protective cap. The sprinkler and cup are easily installed into the sprinkler fitting using the Model RC1 Sprinkler Wrench. The cover plate assembly is attached to the sprinkler cup using a flexible tooth threaded engagement. The cover plate is attached to the skirt using 135°F (57°C) ordinary temperature classification solder.

Installation

Sprinklers must be installed in purpose-designed Reliable nozzle wrench. Key types can be found in the data sheet. Concealed models are installed under 57ºC with the CCP model of the cover.

Sprinklers capsule protector is protected by a glass capsule during transport, handling and installation. Glass capsule protector is removed after installation. Removing protection prematurely may expose the sprinkler damage. Capsule protector is removed by opening them by hand. Avoid using the tools, so do not damage the glass capsule.

Models

F1FR56 QREC
Pendent
Horizontal Sidewall EC-8

F1FR56 QREC Concealed
Extended Coverage Pendent (+CCP cover plate)

Listings and Approvals

1. Listed by Underwriters Laboratories, Inc. and
Certified for Canada (cULus)
2. Factory Mutual Approvals (FM)

UL Listing Category
Sprinklers, Automatic & Open
Quick Response Extended Coverage Sprinkler (VNIV)

Temperature Rating

Sprinkler Temp. Max.Ambient Temp. Bulb Color
57ºC 38ºC Orange
68ºC 38ºC Red