Model F1 Res Pendent sprinklers are fast response sprinklers combining excellent durability, high sensitivity glass-bulb and low profile decorative design. The F1 Res Horizontal Sidewall sprinklers are equally attractive when above ceiling piping cannot be used. The 3mm glass-bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection application needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive element, glass bulb or link to actuate, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire.The temperature-sensitive part of the sprinklers is 3 mm glass capsule fuse or lock. Standard sprinkler nozzles durability combined with a stylish appearance. With decorative frames, they are extremely versatile and easy to install cleanly.

Technical Specifications

Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass-bulb
Sprinkler Frame: Brass Casting
Sprinklers’ Pressure Rating: 12 bar (tehdastestattu 34 bar)
Thread size: ½”NPT tai ½”BSPT
Nominal K-values:
gpm/psi½ (Lpm/bar½)
• 3.0 (43) – F1 Res 30 Pendent
• 4.9 (71) – F1 Res 49 Pendent
• 5.8 (84) – F1 Res 58 Pendent & HSW
• 7.6 (109) – F1 Res 76 Pendent
• 4.4 (63) – F1 Res 44 HSW
Water density: min. 2,0 mm/min

Models

1. F1 Res 30 Pendent
2. F1 Res 30 Pendent (Recessed)
3. F1 Res 49 Pendent
4. F1 Res 49 Pendent (Recessed)
5. F1 Res 58 Pendent
6. F1 Res 58 Pendent (Recessed)
7. F1 Res 76 Pendent
8. F1 Res 76 Pendent (Recessed)
9. F1 Res 30 CCP Pendent
10. F1 Res 49 CCP Pendent
11. F1 Res 58 CCP Pendent
12. F1 Res 76 CCP Pendent
13. F1 Res 44 HSW
14. F1 Res 44 HSW (Recessed)
15. F1 Res 58 HSW
16. F1 Res 58 HSWX
17. KRes58 HSWX
18. F1 Res 58 HSW HSW (Recessed)
19. F1 Res 44 SWC

Listings and Approvals

1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus)

UL listing categories
Residential Automatic Sprinkler (VKKW)