- Datasheet
- Distribution Patterns B
- Distribution Patterns FM Open Window
- Distribution Patterns FM Cornice
Description
Reliable B- and FM-open window nozzles and FM-open cornice nozzles, which are mounted to spray water in a predetermined region. The nozzles are designed for outdoor use. High Velocity Spray Nozzles System can be operated manually or fast pneumatically, hydraulically or electrically by controlled valves. The nozzles are available in bronze, chrome or lead plated. No waterway protection is provided.
Model B – Open Window Nozzle
This Nozzle is designed to provide protection for exterior wall, windows and other openings of buildings that may be subjected to fire spreading from neighboring properties. It is usually installed at the top of windows or other openings. The Model B Open Window Sprinkler may be utilized in the protection of such things as horizontal, multi–tier veneer dryers and structural steel members not requiring fire–resistant insulation. For such uses the authority having jurisdiction should be consulted for the acceptance of the application. A Model B Open Window Sprinkler distributes water in a fan–shaped pattern against the exterior surface, resulting in a water curtain extending all the way to the ground.
UL-listed, FM-approved
Orifice size | Thread | K-value | Overall length | Installation position | Pressure | Distance | Width | SIN |
1/4″ | 1/2″ | 26 | 4,6 cm | Pendent | 0,5 bar 3,7 bar 6,9 bar |
2,4 m 4,6 m 4,9 m |
6,1 m 13,1 m 12,8 m |
R0413 |
5/16″ | 1/2″ | 37 | 4,6 cm | Pendent | 0,3 bar 3,6 bar 6,9 bar |
2,4 m 4,9 m 5,2 m |
6,7 m 12,2 m 12,2 m |
R0414 |
3/8″ | 1/2″ | 50 | 4,6 cm | Pendent | 0,3 bar 3,6 bar 6,9 bar |
2,7 m 5,5 m 5,2 m |
6,7 m 4,9 m 5,2 m |
R0415 |
Model FM – Open Window Nozzle
This Nozzle performs the same basic function for the protection of exterior walls and their openings as the Model B Open Window Sprinkler. Having a larger orifice than the Model B Open Window Sprinkler, it distributes a larger volume of water.
FM-approved
Orifice size | Thread | K-value | Overall length | Installation position | Pressure | Angle | Width | SIN |
1/2″ | 1/2″ | 95 | 7,6 cm | Pendent | 0,5 bar 3,7 bar 6,9 bar |
119º 121º 119º |
2,7 m 4,6 m 4,6 m |
R0418 |
5/8″ | 3/4″ | 144 | 4,6 cm | Pendent | 0,5 bar 3,6 bar 6,9 bar |
149º 150º 150º |
3,4 m 6+ m 6+ m |
R0416 |
3/4″ | 3/4″ | 207 | 4,6 cm | Pendent | 0,5 bar 3,6 bar 6,9 bar |
150º 150º 151º |
4,9 m 6+ m 6+ m |
R0411 |
Model FM – Open Cornice Nozzle
This Nozzle is installed under building cornices and ridges to provide protection for these exterior surfaces. Because of the special contour of the deflector, it distributes water equally on opposite sides in a narrow fan–shaped curtain. The distribution pattern covers the underside of cornices and ridges with water.
FM-approved
Orifice size | Thread | K-value | Overall length | Installation position | Pressure | Angle | Width | SIN |
1/2″ | 1/2″ | 94 | 6,7 cm | Upright | 0,5 bar 3,7 bar 6,9 bar |
136º 138º 140º |
6,1 m 13,4 m 13,4 m |
R0428 |
5/8″ | 3/4″ | 141 | 6,7 cm | Upright | 0,5 bar 3,6 bar 6,9 bar |
139º 141º 141º |
8,5 m 13,4 m 13,4 m |
R0426 |