Reliable Logo
Approvals
SIN-numbers
R0413, R0414, R0415, R0411, R0416, R0418, R0426, R0428

Description

Reliable B- and FM-open window nozzles and FM-open cornice nozzles, which are mounted to spray water in a predetermined region. The nozzles are designed for outdoor use. High Velocity Spray Nozzles System can be operated manually or fast pneumatically, hydraulically or electrically by controlled valves. The nozzles are available in bronze, chrome or lead plated. No waterway protection is provided.

Model B – Open Window Nozzle

This Nozzle is designed to provide protection for exterior wall, windows and other openings of buildings that may be subjected to fire spreading from neighboring properties. It is usually installed at the top of windows or other openings. The Model B Open Window Sprinkler may be utilized in the protection of such things as horizontal, multi–tier veneer dryers and structural steel members not requiring fire–resistant insulation. For such uses the authority having jurisdiction should be consulted for the acceptance of the application. A Model B Open Window Sprinkler distributes water in a fan–shaped pattern against the exterior surface, resulting in a water curtain extending all the way to the ground.

UL-listed, FM-approved

Model B – technical Specifications

Orifice size Thread K-value Overall length Installation position Pressure Distance Width SIN
1/4″ 1/2″ 26 4,6 cm Pendent 0,5 bar
3,7 bar
6,9 bar
2,4 m
4,6 m
4,9 m
6,1 m
13,1 m
12,8 m
R0413
5/16″ 1/2″ 37 4,6 cm Pendent 0,3 bar
3,6 bar
6,9 bar
2,4 m
4,9 m
5,2 m
6,7 m
12,2 m
12,2 m
R0414
3/8″ 1/2″ 50 4,6 cm Pendent 0,3 bar
3,6 bar
6,9 bar
2,7 m
5,5 m
5,2 m
6,7 m
4,9 m
5,2 m
R0415

Model FM – Open Window Nozzle

This Nozzle performs the same basic function for the protection of exterior walls and their openings as the Model B Open Window Sprinkler. Having a larger orifice than the Model B Open Window Sprinkler, it distributes a larger volume of water.

FM-approved

Model FM Open Window Nozzle – technical Specifications

Orifice size Thread K-value Overall length Installation position Pressure Angle Width SIN
1/2″ 1/2″ 95 7,6 cm Pendent 0,5 bar
3,7 bar
6,9 bar
119º
121º
119º
2,7 m
4,6 m
4,6 m
R0418
5/8″ 3/4″ 144 4,6 cm Pendent 0,5 bar
3,6 bar
6,9 bar
149º
150º
150º
3,4 m
6+ m
6+ m
R0416
3/4″ 3/4″ 207 4,6 cm Pendent 0,5 bar
3,6 bar
6,9 bar
150º
150º
151º
4,9 m
6+ m
6+ m
R0411

Model FM – Open Cornice Nozzle

This Nozzle is installed under building cornices and ridges to provide protection for these exterior surfaces. Because of the special contour of the deflector, it distributes water equally on opposite sides in a narrow fan–shaped curtain. The distribution pattern covers the underside of cornices and ridges with water.

FM-approved

Model FM Open COrnice Nozzle – technical Specifications

Orifice size Thread K-value Overall length Installation position Pressure Angle Width SIN
1/2″ 1/2″ 94 6,7 cm Upright 0,5 bar
3,7 bar
6,9 bar
136º
138º
140º
6,1 m
13,4 m
13,4 m
R0428
5/8″ 3/4″ 141 6,7 cm Upright 0,5 bar
3,6 bar
6,9 bar
139º
141º
141º
8,5 m
13,4 m
13,4 m
R0426