Description
Reliable Model F3-80 Dry Sprinklers are standard response sprinklers utilizing a durable 5mm frangible glass bulb.
Model F3-80 Dry Sprinklers are intended for use in dry and preaction systems and in areas subjected to freezing temperatures, such as freezers and unheated portions inside and outside buildings.
Models
• Pendent
• Pendent HB (long escutcheon)
• Recessed FP Pendent
• Concealed pendent + CCP-cover
• Horizontal Sidewall
• Horizontal Sidewall HB (long escutcheon)
• Recessed FP Horizontal Sidewall
Technical specifications
K-value: 115
Thread size: ISO7-1R1 or 1″ NPT
Max.operating pressure: 12 bar
Length: 2″-36” (51mm-922mm)
*See datasheet to determine the right length (A-dimension)
Features
1. 38 mm escutcheon adjustment on pendent sprinkler
2. 25 mm escutcheon adjustment on pendent HB sprinkler
3. 12 mm escutcheon adjustment on recessed sprinkler with push-on/thread-off FP Model escutcheon ring
4. 10 mm cover plate adjustment on concealed sprinkler with push-on/ thread-off CCP cover
5. Available in a variety of plated and painted finishes
6. Polyester Coated or Electroless Nickel PTFE (Teflon®)Plated Corrosion Resistant Sprinklers
Listings and approvals
1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus)
Model | Response | Approvals |
Pendent Recessed FP Pendent Piilosuutin pendent (RA6012) |
Standard Response | cULus, NYC |
HSW HSW HB (long escutcheon) Recessed HSW FP (RA6032) |
Standard Response | cULus*, NYC* |
* cULus Listing and NYC for Light Hazard (existing) and Ordinary Hazard only
Sprinkler temp. | Max.ambient temp. | Bulb color |
57ºC | 38ºC | Orange |
68ºC | 38ºC | Red |
79ºC | 66ºC | Yellow |
93ºC | 66ºC | Green |
141ºC | 107ºC | Blue |